Lutron DW-6093 – 3 Phase Power Quality Analyzer

Availability:

Stok 5


The DW-6093 3-Phase Power Analyzer offers accurate and reliable measurements for multi-phase power systems, making it an essential tool for various applications in electrical testing, industrial environments, and maintenance.

Status Barang: Ready

Kondisi: Baru

Minimal Order: 1 pcs

Rp19.608.150,0

Stok 5

Bagikan:

3 PHASE POWER ANALYZER
Model: DW-6093

FEATURES:
◆ Analysis for 3 phase multi-power system, 1P/2W, 1P/3W, 3P/3W, 3P/4W
◆ 3 current probes (CP-1201) are included, if change the current probes, the calibration procedures are not necessary
◆ Current probe input signal/ranges with selection: Input signal (ACV): 200 mV/300 mV/500 mV/1 V/2 V/3 V Ranges (ACA): 20 A/200 A/2000 A/30 A/300 A/3000 A/6000 A
◆ Meter can cooperate with other universal current probes
◆ Voltage amp; Current are the True RMS value
◆ True Power (KW, MW, GW)
◆ Apparent Power (KVA, MVA, GVA)
◆ Reactive Power (KVAR, MVAR, GVAR)
◆ Watt-Hour (WH, SH, QH, PFH)
◆ Power Factor (PF), Phase Angle (Degree)
◆ Voltage range: 10 to 600 ACV
◆ Current range: 0.2 to 1200 ACA, CP-1201
◆ Programmable CT ratio (1 to 600) and PT ratio (1 to 1000)
◆ ACV input impedance is 10 Mega ohms
◆ Safety Standard : IEC 1010, CAT III 600V
◆ Built-in clock and Calendar, real time data record with SD memory card , sampling time can be set from 2 to 7200 seconds. Just slot the SD card into the computer, all the measured values with the time information ( year, month, data, hour, minute, second ) can be downloaded to the Excel directly, then user can make the further data analysis by themselves.
◆ Powered by AA (UM-3) DC 1.5 V x 8 PCs batteries ( Alkaline type ) or DC 9V adapter
◆ Computer data output, can cooperate with optional USB Cable/USB-01, RS232 cable/UPCB-02 and Data Acquisition software, SW-U811, SW-E802.

EACH UNIT INCLUDES WITH:
◆ Instruction Manual (1 PC)
◆ Test Leads (1 Set, 4 PCs)
◆ Alligator Clips (1 Set, 4 PCs)
◆ Clamp Probes (3 PCs, CP-1201)
◆ AC to DC 9V Adapter (1 PC)
◆ SD Card (2 GB)
◆ Carrying Bag (1 PC)

OPTIONAL ACCESSORIES:
◆ Flexible 3000 Amp current probe, CP-3000
◆ Flexible 6000 Amp current probe, CP-6001
◆ USB Cable, USB-01
◆ RS232 cable, UPCB-02
◆ Data Acquisition software, SW-U811-WIN

SKU: L-DW6093 Kategori: Brand:
Berat 6 kg

GENERAL SPECIFICATIONS:

Circuit

Custom one-chip of microprocessor LSI circuit

Display

* LCD Size :
81.4 X 61 mm ( 3.2 X 2.4 inch )

* Dot Matrix LCD (320 X 240 pixels ) with back light.

Measurement

  • *  ACV
  • *  ACA
  • *  AC WATT ( True Power )

    AC WATT( Apparent Power )

    AC WATT( Reactive Power )

  • *  Power factor
  • *  Phase angle
  • *  Frequency

Wire connections

1P/2W, 1P/3W, 3P/3W, 3P/4W.

Voltage ranges

10 ACV to 600 ACV, auto range.

Current probe input signal and range

  • *  Currentprobeinputsignalvolage(ACV): 200mV/300mV/500mV/1V/2V/3V.
  • *  Currentprobeinputcurrentrange(ACA): 20 A/200A/2000A (1200 A)/30A/300A/3000A
  • *  Metercancooperatetheuniversalcurrentprobe.

Safety standard

IEC1010 CAT III 600 V.

ACV input impedance

10 Mega ohms.

Range select

ACV

Auto range.

ACA

Manual range.

Clamp frequency response

40 Hz to 1 KHz.

Spec. tested frequency

45 to 65 Hz.

Over load protection

ACV

720 ACV rms

ACA

1300 ACA with clamp probe * For the Clamp ,CP-1201

Over Indicator

* LCD display show ” OL “.
* The data save into the SD card will show

” 9999 ” or ” 999 ” ( overleap the decimal point ).

Under Indicator

* LCD display show ” UR “.
* The data save into the SD card will show

” 9999 ” or ” 999 ” ( overleap the decimal point ).

Data Hold

Freeze the display reading.

Data Record

SD Card Record.

Sampling Time

Approx. 1 second.

Power ON/OFF

Manual OFF by push button.

Real time data logger

* Real time data logger, saved the data into SD memory card and down load the all the measured value with the time information ( year/month/data/ hour/minute/second ) down load

to the Excel

* Integration time for data logger :
2 seconds to 7200 seconds, the during of setting step are 2 seconds.

Data Output USB/RS232 * Computer

interface

RS232 computer serial interface :

  • *  Connect the optional USB cable USB-01 will get the USB plug.
  • *  Connect the optional RS232 cable UPCB-02 will get the RS232
    plug.

Operating Temperature

0 to 50°C ( 32 to 122°F ).

Operating Humidity

Less than 80% R.H..

Power Supply

* DC1.5V,AA(UM-3)BatteryX8PCs (Alkaline or heavy-duty battery).

* AC to DC 9V power adapter.

Power Consumption

* Meter : 300 DCmA. * Clamp : 34 DCmA.

Clamp max. conductor Size

50 mm ( 2.0 inch ) Dia.
* For the Clamp ,CP-1201

Weight

* Meter : 948g ( includes batteries ) * Clamp ( includded cable ) : 467g

Dimension

Meter :
225 X 125 X 64 mm
( 8.86 X 4.92 X 2.52 inch )

Dimension

Clamp :
210 X 64 X 33mm
( 8.3 X 2.5 X 1.3 inch )

Clamp Jaw : 86 mm (3.4 inch)- outside

Accessories Included

* Instruction manual…………… 1 PC
* Test Leads (TL88-4AT)………..1 Set (4 PCs) * Alligator clips (TL88-4AC) 1 Set (4 PCs) * Clamp Probe ( CP-1201 )……..3 PCs
* AC to DC 9V adapter…………..1 PC
* SD card ( 2 G )……………….. 1 PC
* Carrying bag……………………. 1 PC

Optional Accessories

  • *  2000 Amp current probe, CP-2000
  • *  200 Amp current probe, CP-200
  • *  Flexible 3000 Amp current probe,

    CP-3000

  • *  USB Cable , USB-01
  • *  RS232 cable, UPCB-02
  • *  Data Acquisition software, SW-U811

ELECTRICAL SPECIFICATIONS:

ACV

Range

Resolution

Accuracy

10.0V to 600.0V
* Phase to neutral line

0.1V

± (0.5%+0.5V)

10.0V to 600.0V * Phase to phase

ACA

Range

Resolution

Accuracy

20A

0.001A, < 10 A 0.01A, ≧ 10 A

± (0.5%+0.1A)

200A

0.01A, < 100 A 0.1A, ≧ 100 A

± (0.5%+0.5A)

1200A

0.1A, < 1000 A 1A, ≧ 1000 A

± (0.5%+5A)

Power factor

Range

Resolution

Accuracy

0.00 to 1.00

0.01

± 0.04

Remark :
* PFH : Long term power factor * PFΣ :

For 3Φ 4W, 3Φ 3W
PFΣ =(PF1+PF2+PF3)/3

For 1Φ 3W
PFΣ =(PF1+PF2)/2

Φ ( Phase angle )

Range

Resolution

Accuracy

-180° to 180°

0.1°

±1° *ACOS(PF)

Frequency

Range

Resolution

Accuracy

45 to 65 Hz

0.1 Hz

0.1 Hz

Active (Real) Power

Range

Resolution

Accuracy

0.000 to 9.999 KW

*0.001/0.01/0.1 KW

± (1%+0.008KW)

10.00 to 99.99 KW

*0.01/0.1 KW

± (1%+0.08KW)

100.0 to 999.9 KW

0.1 KW

± (1%+0.8KW)

1.000 to 9.999 MW

0.001 MW

± (1%+0.008MW)

Apparent Power

Range

Resolution

Accuracy

0.000 to 9.999 KVA

*0.001/0.01/0.1KVA

± (1%+0.008KVA)

10.00 to 99.99 KVA

*0.01/0.1 KVA

± (1%+0.08KVA)

100.0 to 999.9 KVA

0.1 KVA

± (1%+0.8KVA)

1.000 to 9.999 MVA

0.001 MVA

± (1%+0.008MVA)

Reactive Power

Range

Resolution

Accuracy

0.000 to 9.999 KVAR

*0.001/0.01/0.1KVAR

± (1%+0.008 KVAR)

10.00 to 99.99 KVAR

*0.01/0.1 KVAR

± (1%+0.08 KVAR)

100.0 to 999.9 KVAR

0.1 KVAR

± (1%+0.8 KVAR)

1.000 to 9.999 MVAR

0.001 MVAR

± (1%+0.008 MVAR)

* : The resolution is changed according the different ACA range.

Watt Hour ( Active Power Hour) : WH

Range

Resolution

Accuracy

0.000 to 9.999 KWH

0.001 KWH

± (2%+0.008 KWH)

10.00 to 99.99 KWH

0.01 KWH

± (2%+0.08 KWH)

100.0 to 999.9 KWH

0.1 KWH

± (2%+0.8 KWH)

1.000 to 9.999 MWH

0.001 MWH

± (2%+0.008 MWH)

VA Hour ( Apparent Power Hour ) : SH

Range

Resolution

Accuracy

0.000 to 9.999 KVAH

0.001 KVARH

± (2%+0.008 KVARH)

10.00 to 99.99 KVARH

0.01 KVARH

± (2%+0.08 KVARH)

100.0 to 999.9 KVARH

0.1 KVARH

± (2%+0.8 KVARH)

1.000 to 9.999 MVARH

0.001 MVARH

± (2%+0.008 MVARH)

VAR Hour ( Reactive Power Hour ) : QH

Range

Resolution

Accuracy

0.000 to 9.999 KVARH

0.001 KVARH

± (2%+0.008 KVARH)

10.00 to 99.99 KVARH

0.01 KVARH

± (2%+0.08 KVARH)

100.0 to 999.9 KVARH

0.1 KVARH

± (2%+0.8 KVARH)

1.000 to 9.999 MVARH

0.001 MVARH

± (2%+0.008 MVARH)