Seaward PrimeTest 100 – Portable Appliance Tester (PAT Tester)

Availability:

3 in stock


The PrimeTest 100 portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication and test result values. A simple range of tests are selected at the push of a button to test earthed equipment, double insulated equipment or mains cords and leads.

Status Barang: Preorder (6 Minggu)

Kondisi: Baru

Minimal Order: 1 pcs

⚠️ Barang ini Pre-Order (Full Payment). Pengiriman akan dilakukan setelah barang tersedia.

Bagikan:

Seaward PrimeTest 100
Portable Appliance Tester
Part Number: 344A910

OVERVIEW:
The PrimeTest 100 portable appliance tester is battery powered and handheld to allow for fast and efficient testing with clear PASS/FAIL indication and test result values. A simple range of tests are selected at the push of a button to test earthed equipment, double insulated equipment or mains cords and leads.

FEATURES:
◆ Simple to use push button operation
◆ Easy-to-read LCD display – shows simple pass/fail indication
◆ Accurate and reliable earth continuity testing
◆  BSEN50699 and IET CoP 5th Edition compliant
◆  Compatible with free PATMobile app – enables you to log results, export your data, tag photos and print results*
◆ Selectable 250V/500V Insulation test
◆ Long lead test
◆ User selectable earth continuity limits
◆ Class II FE Test

EACH UNIT INCLUDES WITH:
◆ PrimeTest 100 (344A910)
◆ Carry Case (71G082)
◆ Black Test Lead 1m (347A002)
◆ UK IEC mains cord 0.5m (300A002)
◆ Operating Instructions

SKU: 344A910 Category: Brand:
Weight1 kg
Earth Continuity
Test Current+/- 200mA DC
Display Range0.00 – 19.99Ω
Pass Value0.1Ω/0.2Ω/0.3Ω
IEC Lead Test
Tests PerformedEarth continuity, Insulation resistance, Live, neutral continuity and polarity
Equivalent Leakage Class II
Test Voltage40V, 50Hz AC nominal
Display Range0.10 – 9.99mA
Pass Value0.5 / 5.0mA
Insulation Range
Test Voltages250V/500VDC
Display Range0.20 – 19.99MΩ
Pass Value1MΩ/2MΩ
Equivalent Leakage Class I
Test Voltage40V, 50Hz AC nominal
Display Range0.10 – 9.99mA
Pass Value3.5 / 5.0mA
Power Socket Test
Input Voltage Range230V +10% – 15% AC
IndicatorsLine to earth voltage, Line to neutral voltage, Neutral earth