KYORITSU 4200
Earth Tester
KYORITSU 4200
Earth Clamp Tester
Call 022 7106162
Earth Tester
KYORITSU 4200
Earth Clamp Tester
Call 022 7106162
Features:
Note:
A single earthing can not be measured. (Only for Multiple Earthing System)
4200 (769 KB)
Function | Range | Resolution | Measuring range | Accuracy | ||||
Earth resistance Auto range | 20Ω | 0.01Ω* | 0.00~20.99Ω | |±1.5%±0.05Ω | ||||
200Ω | 0.1Ω | 16.0~99.9Ω | |±2%±0.5Ω | |||||
100.0~209.9Ω | |±3%±2Ω | |||||||
1200Ω | 1Ω | 160~399Ω | |±5%±5Ω | |||||
400~599Ω | |±10%±10Ω | |||||||
10Ω | 600~1260Ω | --- | ||||||
AC current (50Hz / 60Hz) Auto range | 100mA | 0.1mA | 0.0~104.9mA | |±2%±0.7mA | ||||
1000mA | 1mA | 80~1049mA | |±2% | |||||
10A | 0.01A | 0.80~10.49A | ||||||
30A | 0.1A | 8.0~31.5A | ||||||
Operating system |
| |||||||
Over-range indication | "OL" is displayed when input exceeds the upper limit of a measuring range | |||||||
Response time | Approx.7 seconds (Earth resistance) Approx.2 seconds (AC current) | |||||||
Sample rate | Approx. 1 times per second | |||||||
Power source | DC6V : R6P (sizeAA manganese battery) × 4pcs, or LR6 (sizeAA alkaline battery) × 4pcs | |||||||
Current consumption | Approx. 50mA (max. 100mA) | |||||||
Measurement time | Approx. 12 hours (when R6P is used) Approx. 24 hours (when LR6 is used) | |||||||
Auto power-off | Turns power off about 10 minutes after the last button operation. | |||||||
Applicable standards | IEC 61010-1 : 2001 (CAT.IV 300V Pollution degree2) | |||||||
Withstand voltage | AC5320Vrms / 5 seconds Between the Transformer jaws fitted parts and Case enclosure (except for jaws) | |||||||
Conductor size | Approx. 32mm max. | |||||||
Dimension | 246(L) × 120(W) × 54(D)mm | |||||||
Weight | Approx. 780g (including batteries) | |||||||
Accessories | Battery R6P : 4pcs Instruction manual : 1pc 8304 (Resister for operation check : 1pc) 9128 (Hard case : 1pc) |
•Crest factor < 3 (50Hz / 60Hz, peak value shall not exceed 60A)
*4 counts or less are corrected to 0.
Why earth resistance can be found by only clamping it?
Rx, is defined as earth resistance under test, and R1, R2...Rn are defined as earth resistance of other measuring objects. | ![]() |
These earth resistances, R1, R2, Rn can be considered that they are connected in parallel. And they can be regarded as a combined resistance Rs. The Rs can be regarded small enough against Rx since a combined resistance consists of several resistances. Following is an equivalent circuit diagram of this circuit. | ![]() |
Voltage V is applied to the object (Resistance Rx) measured from the voltage injection transformer CT1, and the current I corresponding to the earth resistance is flowed.The current I is detected with detection transformer CT2, and object (Resistance Rx) measured can be put out by the calculation. (refer to the right diagram) | ![]() |